Western Telematic Switch PTS 8NE15 1 User Manual

WTI Part No.: 14124  
Rev.: A  
PTS Series  
Automatic Power Transfer Switch  
Models Covered:  
PTS-8NE15-1  
PTS-9CM20-2  
Quick Start Guide  
 
1. Introduction  
This Quick Start Guide describes the installation procedure for the PTS series  
hardware. The PTS is essentially a power fallback switch, that automatically  
switches power from a primary input to a secondary input when power to the  
primary input is lost or interrupted.  
2. Hardware Installation  
Apply Power to the MPC  
Refer to the warnings and cautions at the beginning of this guide and the  
power rating nameplate on the PTS back panel, and then connect the unit to  
two appropriate power sources. For units with detachable power input cables,  
connect the power input cables to the power inlets, install the cable keepers, and  
then connect the primary power input cable to your primary power supply and  
the secondary power input cable to your secondary power supply. Refer to the  
table below for information concerning power requirements and maximum loads.  
Input  
Feeds (x2)  
Input  
Voltage  
Max. Load  
per Outlet  
Max. Load  
per Unit  
Model No.  
Outlets  
PTS-8NE15-1  
PTS-9CM20-2  
15 Amps  
20 Amps  
100 to 120 VAC  
200 to 240 VAC  
12 Amps  
8 ea. NEMA 5-15R  
12 Amps*  
16 Amps*  
10/16 Amps  
8 ea. IEC-60320-C13  
1 ea. IEC-60320-C19  
*
In accordance with UL requirements, this value has been de-rated to 80%.  
Power Input Feeds:  
PTS-8NE15-1: Two (2) IEC-60320-C14 Inlets.  
PTS-9CM20-2: Two (2) IEC-60320-C20 Inlets.  
Notes:  
• After connecting your power cables to the PTS unit, make certain to  
secure the cables in order to prevent accidental disconnection.  
• PTS-1 series units are designed for switching power input lines that  
are typically 120 VAC. If a power input lower than 120 VAC is  
connected to a PTS-1 unit, then power switching features will not  
function correctly.  
• PTS-2 series units are designed for switching power input lines that  
are typically 240 VAC. If a power input lower than 240 VAC is  
connected to a PTS-2 unit, then power switching features will not  
function correctly.  
Page 3  
 
3. Operation  
When properly installed, the PTS will automatically switch power from the  
primary input to the secondary input when the power to the primary input is  
interrupted. After switching from primary to secondary, the PTS will also switch  
power back to the primary input when power to the primary input is restored.  
Note that the "Input Power" LEDs on the PTS front panel will light to indicate  
which power input is active. If the "Primary" LED is lit, this indicates that the  
Primary Power source is active; if the "Secondary" LED is lit, this indicates that  
the Secondary power source is active.  
FCC Part 15 Regulation  
This equipment has been tested and found to comply with the limits for a Class A digital device,  
pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection  
against harmful interference in a residential installation. This equipment generates, uses, and can  
radiate radio frequency energy, and if not installed and used in accordance with the instructions, may  
cause harmful interference to radio communications. However, there is no guarantee that interference  
will not occur in a particular installation. If this equipment does cause harmful interference to radio  
or television reception, which can be determined by turning the equipment off and on, the user is  
encouraged to try to correct the interference by one or more of the following measures:  
Reorient or relocate the receiving antenna.  
Increase the separation between the equipment and receiver.  
Plug the equipment into an outlet on a circuit that is different from the one used by the receiver.  
Consult the dealer or an experienced radio/TV technician for help.  
This device complies with Part 15 of the FCC rules. Operation of this device is subject to the  
following conditions: (1) This device may not cause harmful interference, and (2) this device must  
accept any interference that may cause undesired operation.  
WARNING: Changes or modifications to this unit not expressly approved by the  
party responsible for compliance could void the user’s authority to operate the  
equipment  
Industry Canada - EMI Information  
This Class A digital apparatus complies with Canadian ICES-003.  
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.  
5 Sterling • Irvine • California 92618  
(949) 586-9950 • Toll Free: 1-800-854-7226  
 

Well Traveled Living Patio Heater 60698 User Manual
Westinghouse Model Vehicle DWM32H1Y1 User Manual
Whirlpool Dishwasher DP8700XTN0 User Manual
Whirlpool Freezer RT12FC User Manual
Wolfgang Puck Slow Cooker WPSC0017C User Manual
Woodstock Planer W1210 User Manual
Yamaha Electronic Keyboard DX7 User Manual
Yamaha Recording Equipment DTR2 User Manual
Yamaha Stereo Amplifier A150 User Manual
Zanussi Dishwasher 864516 User Manual